Introduction CET3-AP-CRA-AH-50X-SA-122398 Safety Sensing Euchner

- CET3-AP-CRA-AH-50X-SA-122398 Safety Euchner Switch  Currently being distributed exclusively and widely by Jon-Jul Company in the Vietnamese market.

CET3-AP-CRA-AH-50X-SA-122398 (Order no. 122398)

- Safety switch with protection lock and integrated rating electronics
- Locking force up to 6500 N
- Short circuit monitoring
- 2 safety outputs (semiconductor output)
- Class 4/PL e according to EN ISO 13849-1
- With 1 M12 plug, 8 pins
- Unicode code plate
- Door monitoring output
- Door position LED indicator
- Approach A (delivery status)

Approach

Horizontal

Adjustable in 90° steps

Safety switch
The device can only be operated with the CET-A-... actuator.

Important : Actuator must be ordered separately.

Unicode Evaluation
Each actuator is highly encoded (unicode). The switch only detects pre-taught actuators. Additional actuators can be tutored. Only the last actuator taught is detected.

Electromagnetic operating voltage
DC 24V +10%, -15%
Protection lock type
CET3 Closed circuit current principle, spring force protection lock. Release by applying voltage to the protective lock solenoid valve. Door position is also tracked. Door monitoring output OUT D is set HIGH as soon as the actuator above the plunger expands (state: door closed, protection lock inactive). Output OUT D also remains set when the protection lock is activated.

LED function display
Status LED 

LED DIAMETER Diagnostic LED

The 1st LED lights up when the solenoid is energized

The 2g LED lights up when the door is closed

Additional connections
EXTERNAL Output monitoring (semiconductor)

OUT D Door monitoring output

List according to EN ISO 13849-1
Due to the two designed redundant semiconductor outputs (safety outputs) there is an internal monitoring function suitable for:

Class 4/PL e according to EN ISO 13849-1
The safety characteristics stated apply to all installation directions of the safety switch.
Important: To achieve the stated category according to EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.

Technical specifications CET3-AP-CRA-AH-50X-SA-122398 Safety Sensing Euchner

 

Workspace

Repeat accuracy R  
according to EN 60947-5-2 10 %

Electrical connection values

Fuse  
external (operating voltage UB) 0.25 ... 8 A
external (solenoid operating voltage UCM) 0.5 ... 8 A
Power consumption  
Solenoid 11 W
Connecting cable 30V DC, 2A 
Operating voltage DC  
UB 24 V DC -15% ... +15% reverse polarity protected, regulated, residual ripple<5%, PELV 
LED 24 V DC -15% V DC ... +10% V DC
EMC protection requirements Acc. to EN IEC 60947-5-3
Utilization category  
DC-13 24 V 200 mA 
Solenoid operating voltage DC  
UCM 24 V DC -15% ... +10% reverse polarity protected, regulated, residual ripple<5%, PELV
Solenoid duty cycle 100 %
Risk time according to EN 60947-5-3 max. 400 ms
Switching load  
according to UL 24V DC, Class 2 
Safety class  
EN IEC 61140 III
Current consumption  
ICM 450 mA
B 80 mA
Test pulse duration max. 0.3 ms 
Degree of contamination (external, according to EN 60947-1) 3
  Monitoring output OUT D
Output type p-switching, short circuit-proof
Output voltage  
OUT D 0.8xUB ... UB V DC
Switching current  
OUT D 1 ... 50 mA
Switching delay from state change max. 700 ms
  Monitoring output OUT
Output type p-switching, short circuit-proof
Output voltage  
OUT 0.8xUB ... UB V DC
Switching current  
OUT 1 ... 50 mA
Switching delay from state change max. 400 ms

Mechanical values and environment

Approach speed max. 20 m/min
Connection type 1 plug connector M12, 8-pin
Ready delay 1 s
Installation orientation any 
Switching frequency max. 0.5 Hz
Degree of freedom X ±5 mm
Degree of freedom Y ±5 mm
Degree of freedom Z ±4 mm
Mechanical life 2 x 10⁶
Shock and vibration resistance Acc. to EN IEC 60947-5-3
Degree of protection IP67 
Ambient temperature  
at UB = 24 V DC -20 ... +55 °C
Material  
Ramp Stainless steel
Safety switch housing Die-cast aluminum
Locking force Fmax 6500 N
Locking force FZh 5000 N 
Guard locking principle Closed-circuit current principle

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

Mission time 20 and
  Control of guard locking
Category Depending on external control of guard locking
Performance Level Depending on external control of guard locking
PFHD Depending on external control of guard locking
  Monitoring of guard locking and the guard position
Category  
Any installation orientation 4
Performance Level PL e
PFHD  
Any installation orientation 3.1 x 10-9

Miscellaneous

The following applies to the approval according to UL Operation only with UL Class 2 power supply or equivalent measures; see operating instructions

See more technical documents  here

See more technical products  here