SU Electromagnetic Water Meter Aichi Tokei Denki electromagnetic water meter

Technical specifications SU Electromagnetic Water Meter Aichi Tokei Denki electromagnetic water meter

Output Pulse 

Output Form Normally open

Pulse on Time 300ms

Number of Contact 2

Pulse Weight (CH1 and CH2) (L) 100/1000/ 10000 (100)*/1000/10000 * For Meter Size 200mm, 250mm and 300mm, the flow-rate must not exceed 600m3 /h when the pulse weight is 100L/pulse

Kind of Pulse Option0 Forward Net (Forward Pulse – Reverse Pulse) for CH1 and CH2 Option1 CH1: Forward Pulse CH2: Reverse Pulse Option2 CH1: D. Flag (Direction Flag) CH2: Forward Pulse + Reverse Pulse

Maximum Load Current 10mA

Maximum Load Voltage 24V

Interval to Update Pulse 1.8sec

Maximum Transmission Distance 200m (When the cable with 0.01μF/100m or less is used.)